UNIFORM GENERALIZED DOUBLE-SIDED ELIMINATION METHOD AND THE CALCULATION OF THE FAULT CURRENT DISTRIBUTION FOR HYBRID OVERHEAD-UNDERGROUND POWER LINES

邹军,袁建生,周宇坤,马信山
DOI: https://doi.org/10.3321/j.issn:0258-8013.2002.10.022
2002-01-01
Abstract:A uniform generalized double-sided elimination method (GDSEM) based on the concept of line boundaries is presented to calculate the fault current distributions for the hybrid overhead-underground power lines. At first, according to the character of the line boundary, the hybrid power lines are decomposed into several line intervals, and the power line takes on the uniform electrical structure within each lineinterval. Second, it can be obtained the relationship between the boundary currents and the power line current by GDSEM in each line interval. Third, a network algebraic equation group can be formed using the relationship aforementioned byapply-ing the current continuous condition at every boundary point, and then the current distribution of the whole system is determined. The approach presented in this paper issignifican-tly different from the conventional GDSEM. It lies in two aspects: ①The uniform GDSEM can deal with the inter-con-nected power lines with the different electricalstructure, what is more, the number and the manner of the fault point are arbitrary; ②It makes clear that the mathematical nature of the uniform GDSEM is the LU pursuit method of block tri-diagonal matrix, and it also interpolates the recursive procedure of GDSEM from the point of view of mathematics. Typical numerical results prove the validity of the uniformGDSEM. GDSEM can be applied in the analysis ofelectromagnetic environment for power lines.
What problem does this paper attempt to address?