Dynamic state estimation based protection using multi-section multi-layer frequency dependent line model for underground cables in MMC-HVDC grids

Binglin Wang,Yu Liu,Dayou Lu,Ruiyu Pan,Jinhao Qiu
DOI: https://doi.org/10.1016/j.epsr.2023.109836
IF: 3.818
2023-09-27
Electric Power Systems Research
Abstract:A novel dynamic state estimation based protection (DSEBP) method is proposed for underground cables (UGCs), in modular multilevel converter based high-voltage direct current (MMC-HVDC) grids. The method uses the multi-section multi-layer model (MLM) to consider the frequency dependent (FD) line parameters, which are usually neglected by existing protection methods but will significantly impact their performances. The proposed method consists of the following steps: 1) the dynamic line model (DLM) of the healthy UGCs based on a multi-section MLM is proposed to consider the distributed shunt capacitive current and FD line parameters; 2) the DSEBP algorithm is utilized to solve the state variables and formulate the consistency indicator; 3) the trip decision is made when the inconsistency is observed multiple times, and the fault pole identification logic via residuals is presented to minimize the power outage zone. Simulation results present that the proposed DSEBP can dependably and quickly trip the faulted line during internal faults even with large fault impedance, and securely avoid mal-operation during external faults even for bolted faults close to line terminals. The proposed method uses a typical sample rate of 10 kilo samples/sec, and performs robustness towards parameter errors, measurement noises and synchronization errors.
engineering, electrical & electronic
What problem does this paper attempt to address?