Multi-section frequency dependent line model enabled underground cable fault location in MMC-HVDC grids using dynamic state estimation

Binglin Wang,Yu Liu,Dayou Lu,Ruiyu Pan,Kang Yue
DOI: https://doi.org/10.1016/j.ijepes.2023.109322
2023-06-25
Abstract:Line parameters of underground cables (UGCs) in MMC-HVDC grids experience severe frequency dependent characteristics. For fault location of UGCs in MMC-HVDC grids, existing methods usually neglect the frequency dependent line parameters, which limits the fault location accuracy. To overcome this issue, a dynamic state estimation based fault location (DSEFL) method for UGCs in the MMC-HVDC grid is proposed in this paper. Firstly, the dynamic line model of the UGC based on the multi-section multi-layer model is formulated to consider both frequency dependent and distributed characteristics of the line parameters. Next, the DSE algorithm is used to solve the dynamic line model and the consistency indicator with respect to the determined fault location and resistance. Due to the complexity of the multi-layer model, a multi-step algorithm is designed to efficiently obtain the fault location result. Numerical experiments on MMC-HVDC grids verify that the proposed DSEFL method presents higher fault location accuracy for different fault types, locations, and resistances. compared to the existing methods. In addition, the computation burden, effects of measurement noises, parameter errors, and sampling rates are also discussed.
engineering, electrical & electronic
What problem does this paper attempt to address?