Model-free underground cable incipient fault location using two-terminal zero-sequence measurements

Ke Qu,Wenhai Zhang,Shu Zhang,Xianyong Xiao,Yanna Xi,Hongyu Zhang
DOI: https://doi.org/10.1016/j.ijepes.2022.108057
2022-09-01
Abstract:The incipient fault in the underground cable is an intermittent arcing fault with short duration from 1/4 cycle to 4 cycles and can be cleared by itself. It always reoccurs for many times before a permanent fault. The detection and location of incipient faults can help to prevent a permanent fault and enhance power supply reliability. However, accurate incipient fault location is a difficult problem because of its short duration and the non-linearity of the arc model. In this paper, a new idea for accurate underground cable incipient fault location using two-terminal synchronized zero-sequence waveforms is proposed. The two-terminal zero-sequence differential equation is built for fault distance estimation. The proposed algorithm can be applied to locate both sub-cycle and multi-cycle incipient faults. More importantly, an accurate arc model is not required for fault distance estimation. A large number of simulation results in PSCAD/EMTDC validate the effectiveness and accuracy of the proposed method.