Fault location scheme for combined overhead line with underground power cable

El Sayed Tag El Din,Mohamed Mamdouh Abdel Aziz,Doaa khalil Ibrahim,Mahmoud Gilany
DOI: https://doi.org/10.1016/j.epsr.2005.07.008
IF: 3.818
2006-07-01
Electric Power Systems Research
Abstract:This paper presents a fault location scheme for transmission systems consisting of an overhead line combined with an underground power cable. The algorithm requires phasor measurements data from one end of the transmission line and the synchronized measurements at the most far end of the power cable. Fault location is derived using distributed line model, modal transformation theory and Discrete Fourier Transform. The technique can be used on-line or off-line using the data stored in the digital fault recording apparatuses. The proposed scheme has the ability to locate the fault whether it is in the overhead line or in the underground power cable. In addition to, the proposed scheme gives an accurate estimation of the fault resistance at fault location. Extensive simulation studies carried out using MATLAB show that the proposed scheme provides a high accuracy in fault location under various fault conditions.
engineering, electrical & electronic
What problem does this paper attempt to address?