Comparative tests of mixing performance of hot gas plenum with different thermal mixing element in 10MW HTR test module

Zhiyong Huang,Meisheng Yao,Changwen Ma,Yuanhui Xu,Xuedong He,Kelong Yuan
1997-01-01
Abstract:One of the functions of the hot gas plenum at the outlet of the core of HTR-10 is to get sufficient thermal mixing of helium coolant which has uneven radial temperature distribution. On a scale of 1 to 1.5 analogical simulating test model, mixing performances of a kinds of hot gas plenum structures had been experimentally studied. The obtained test results indicate that the hot gas plenum without any mixing element possesses a relatively low mixing degree, and the hot gas plenum with a partition mixer has a very good thermal mixing function for the coolant and can yield a nondimensional temperature mixing degree of more than 94% at the exit of the plenum.