Study on Flashover Voltage of Insulator Strings in High-temperature Water Vapor

张晋,王志龙,欧小波,汲胜昌
DOI: https://doi.org/10.16188/j.isa.1003-8337.2009.02.002
2009-01-01
Abstract:For the purpose of investigating power equipment′ s electrophorus vapor washing technique,the flashover voltage of the polluted insulator strings in high-temperature vapor should be measured and compared with that of the polluted insulator strings in room-temperature fog.The safety of power system should be ensured when the insulators are cleaned by vapor.The insulators are polluted uniformly by brushing.With the NSDD value constant,flashover voltage dependence of insulator strings wetted under different conditions relates the voltage to the SDD value.The results show that in high-temperature vapor surrounding,under the pollution severity lighter than SDD 0.15mg/cm2 and NSDD 1.0mg/cm2,the flashover voltage of insulator strings is higher than the highest operation voltage of system.The system security can be ensured.
What problem does this paper attempt to address?