Numerical Simulation of Corridor-Atria Buffer Effect in High-Rise Building Fires

Ru ZHOU,Jia-peng HE,Jun-cheng JIANG
DOI: https://doi.org/10.3969/j.issn.1673-193x.2011.12.009
2011-01-01
Abstract:In high-rise building fire,a large number of fresh airs will be pressurized into the fire floor when smoke prevention system is used,which dilutes the smoke and reducing the efficiency of mechanical smoke exhaust.The Corridor-atria buffer was put forward to control the smoke which was set between the atria and the corridor.The κ-e three-dimension turbulence model with two equations were used,and the influences of smoke exhaust effect with Corridor-atria buffer were analyzes by simulation.The simulation results show that: in strip corridor,with setting Corridor-atria buffer,the average mass fraction of smoke in the atria was lower than 4.6%,which make the atria more safety.The smoke had two process of cooling in the effect of air curtain in the corridor and the pressure air in the atria,so the smoke of lower temperture was easy to be stagnant status and the tendency of spreading to other floors was reduced obviously,which make a great benefit to the people evacuation in the whole buidling.