Influence of the window's width of the fire room on the smoke overflow behavior

Jing-jing LEI,Ru ZHOU,Jun-cheng JIANG,De-zhi ZHU
DOI: https://doi.org/10.3969/j.issn.1009-0029.2016.12.006
2016-01-01
Fire Science and Technology
Abstract:In order to explore the influence of the window's width on the change of smoke overflow in high-rise buildings fires,an office building in Nanjing was selected as the model background.FDS was used to simulate the change rule of the smoke overflow in the high-rise building fires.The fire source with 1 500 kW located at the middle of room.Six scenarios with different width of window were set to analyze the change of mass flow rate,temperature and current velocity.The result showed that the behavior of flue gas overflow under different openings had certain regularity.With the decrease of the window width,the neutral surface of window raised up,and the mass flow rate of smoke outflow reduced gradually,the temperature decreased gradually and smoke outflow time delayed gradually.Through theoretical analysis and calculation,the simulation results were validated.
What problem does this paper attempt to address?