Performance Comparison of Evaporator with Circuit Number Change in Heat Pump Using R22 and R410A

HUANG Dong,LI Quanxu
DOI: https://doi.org/10.3321/j.issn:0253-987X.2009.07.013
2009-01-01
Abstract:The performance of the indoor coil in a split-type air-source heat pump with R22 and R410A is investigated numerically and compared by EVAP-COND 2.1 version simulation package of NIST.The variation in the evaporator capacity with the circuit number is also analyzed.The results show that the capacity of the evaporator with R410A is greater than that with R22.Moreover,the difference in the capacity of the evaporator with R410A and R22 drops first,and then it rises with the circuit number and the maximum difference is 19.41%.Both the air-and-refrigerant temperature difference and the overall heat transfer coefficient of the evaporator with R410A are greater than those with R22 in the first row,but they are almost equal in the second row.Thus the tube capacity sum in the first row contributes to the difference in the evaporator capacity.In addition,the effect of the air-and-refrigerant temperature difference on the difference in the capacity of the evaporator with R22 and R410A may decrease with the increase of the circuit number while the effect of the overall heat transfer coefficient may increase with the circuit number.
What problem does this paper attempt to address?