Experimental study of ternary mixture R32/R125/R161 as alternative refrigerant to R407C
Xiao-hong HAN,Zhi-wei ZHU,Jie SUN,Yu-ting DONG,Guang-ming CHEN
DOI: https://doi.org/10.3785/j.issn.1008-973X.2007.02.032
2007-01-01
Abstract:A ternary non-azeotropic mixture of R32/R125/R161 as an alternative refrigerant to R407C was studied. The physical characteristics of R32/R125/R161 are similar to those of R407C. Its ozone depleting potential (ODP) is zero and its global warming potential (GWP) is smaller than that of R407C. Without any modification to the system components, experimental tests were performed on a vapor compression refrigeration set with a rotor compressor, which was originally designed for R407C. Experimental results indicate that power consumption, volumetric refrigerating capacity, refrigerating capacity and coefficient of performance (COP) increased, while pressure ratio and discharge temperature decreased with increasing evaporation temperature at different condensation temperature for R32/R125/R161 and R407C. At the same condensation temperature and evaporation temperature, volumetric refrigerating capacity, refrigerating capacity and COP of R25/R125/R161 were superior to those of R407C, and pressure ratio and power consumption of R25/R125/R161 were lower than those of R407C, and discharge temperature was slightly higher than that of R407C at the same working conditions. In addition, COP and volumetric refrigerating capacity increased with increasing subcooled temperature at the same condensation temperature. Therefore, the new refrigerant R32/R125/R161 can be considered as a promising alternative refrigerant to R407C.