Numerical Study of Refrigerant Circuitry in R407C Condensers

DENG bin,TAO Wen-quan,LIN Lan
DOI: https://doi.org/10.3969/j.issn.1005-0329.2005.11.019
2005-01-01
Abstract:Based on the e-NTU,a steady state distributed parameters model was put forward in the numerical simulation of refrigerant circuitry in condensers in this paper.Applying this model,the heat transfer and flow characteristics of four different two-rows condensers are studied.The research indicates that the counter-flow condensers have a better performance than other arrangements.The heat transfer rate of counter-flow condensers is 5%~40% higher than that of parallel-flow condensers and the pressure drop of counter-flow condensers is 3%~10% higher than that of parallel-flow condensers.Between the characteristic comparison of the two refrigerant condensers,the heat transfer rate of R407C condensers is 3%~5% higher than that of R22 condensers and the pressure drop of R407C condensers is 5%~10% lower than that of R22 condensers.R407c is the perfect refrigerant replacement of R22.
What problem does this paper attempt to address?