Comparisons of Heat Transfer Performance of Different Refrigerants in Condenser for Air Conditioning

冯永斌,晏刚,钱文波,张敏,陶锴
DOI: https://doi.org/10.3969/j.issn.1005-0329.2010.01.015
2010-01-01
Abstract:A distributed parameter model for air-conditioning heat exchanger has been developed in this paper.The model has been validated by comparing outputs from the model with test data,given in reference papers.Application of the model is concentrated on studying the alternative refrigerants R32,R410A,R407C and R290 for R22 used in finned-tube condenser.The effects of head-on wind temperature and wind velocity on the flow and heat transfer of condenser are analyzed.The results show that under certain conditions,regardless of increasing the head-on wind temperature or velocity,R407C obtains the largest specific heat load,pressure drop and mass flow rate.Both the pressure drop and the mass flow rate of R290 and R32 are lower than that of R22.Although R410A obtains lower pressure drop,the mass flow rate is relative larger.The mass flow rate of R290 is less than 40% around than that of R22.The coefficient of heat transfer for R290 is larger than that of R22 while the temperature difference for R290 is lower than that of R22.
What problem does this paper attempt to address?