Experimental Study on R-22, R-427A, R-161 and R-290 in Air-Source Heat Pump for Space Heating at Low Ambient Temperatures

Xiaoning Chen,Cichong Liu,Jingye Yang,Jiangping Chen
DOI: https://doi.org/10.1016/j.ijrefrig.2018.08.021
IF: 4.14
2018-01-01
International Journal of Refrigeration
Abstract:To help reduce the warming impacts, this study evaluates the drop-in performances of R-427A, R-161 and R-290 in R-22 air source heat pump with EVI (Economized Vapor Injection). The results show that the IPLV(H) of R-161 and R-290 arises 5∼8% relative to R-22 with EVI on. A reversal occurs between R-290 and the baseline with EVI on, making the IPLV(H) of R-290 superior to that of R-22 by 3.6∼5.2% from worse performance with EVI off. At -20/41°C condition, the capacity and COP of R-290 increase by 38% and 19%, respectively. Considering COP and discharge temperatures, R-290 is better-performed to replace R-22 in high pressure ratio conditions. Based on LCCP (Life Cycle Climate Performance) model, 11% of the equivalent CO2 emission can be reduced by using R-161 and R-290. However, the discharge temperature of R-161 is high in the high pressure ratio condition. R-290 is the most synthetically beneficial alternative.
What problem does this paper attempt to address?