Numerical simulation on air source heat pump using R410A as refrigerant

Shang Pingjun,Dong Yujun,Yuan Xiuling,Huang Dong
DOI: https://doi.org/10.3969/j.issn.1009-8402.2006.05.019
2006-01-01
Abstract:According to a distributed parameter steady-state simulation model of air source heat pump chiller,a simulation code was implemented to calculate the performance of heat pump system using refrigerant R22 and R410A as working fluids under variable steady-state operating conditions. The research results show that system refrigeration capacity increases by(9.4%)~14.7%,the COP decreases by 8.7%~10.6%,the heating capacity increases by (13.2%)~15.1%,and the COP decreases by 1.2%~3.3%.The power consumed by compressor was reduced and COP of the system and steady-state operating performance of the system were improved by methods of employing smaller volume compressor,transforming the refrigerant circuitry arrangement of finned tube heat exchanger coils,changing the heat transfer area of single refrigerant circuitry,or increasing the airflow mass flow rate.After the performance is optimized,the COP of the system for refrigeration and heating are increased by(4.17%)~4.70% and 1.09%~1.25%,respectively.