Analysis of failure element maloperation of a 500 kV bus protection

Yong-hong WANG,Xu-guang GUO
DOI: https://doi.org/10.3969/j.issn.1674-3415.2007.04.021
2007-01-01
Abstract:Along with the extensive application of optocoupler element in the secondary equipment of integrated automatic substations,its operating characteristic also needs much attention.In this paper,an application example of failure protection maloperation is given.It analyzes the action mechanics of the electric capacity discharge.The optocoupler element will misdirect positive pole of DC System grounding,because of the existent electric capacity effect of a long electric cable to the ground.It puts forward the improving measure of using a higher power(8W) intermediate relay restart,and provides useful reference for same category failure protection of the bus.