The Combination of Exhaust Port and Smoke Screen for Smoke Control in Commercial Building

Zeng-hui GUO,Shou-xiang LU,Qi-ze HE,Chang-hai LI
DOI: https://doi.org/10.3969/j.issn.1009-0029.2012.06.010
2012-01-01
Fire Science and Technology
Abstract:Using 3.0MW real diesel pool fire as the fire source,the impact of the height of smoke screen and the location and orientation of the exhaust port on the effect of smoke control in the real commercial building fire scene was studied,with the combination of exhaust port and smoke screen.The size of building is 38m(length) ×21m(width) ×5.4m(height).In the case of certain fire scale,emission of smoke and smoke extraction system start-up time,the height of smoke screen is a key factor influencing the effect of smoke control.The nearer exhaust port is away from the fire source,the better effect smoke control can get.The impact on the smoke control from the orientation of exhaust port is not significant.
What problem does this paper attempt to address?