Application of Selective Non-catalytic Reduction on a Power Plant Boiler

吕洪坤,杨卫娟,周志军,黄镇宇,刘建忠,周俊虎,岑可法
2008-01-01
Abstract:Selective non-catalytic reduction(SNCR) was applied to a HG-410/9.8-YW15 boiler on the base of conventional pulverized-coal reburning process which had been implemented before. The experimental data showed that NOx could be 350 mg/m3(standard condition, 6%O2, dry gas) below under reburning only and 200 mg/m3 below under hybrid reburning/SNCR with NH3 slip lower than 7.6 mg/m3.NOx reduction was much higher when SNCR operated at low load. When setting (NH3)/(NO) to 1.0,NOx reached 160 mg/m3 at 51% boiler load,and the NH3 slip was only 1.14 mg/m3.Further more, SNCR alone could achieved about 38.6% to 73.9% NOx reduction efficiency on the base of reburning at experimental loads. The NH3 slip around front wall was larger than that around back wall at the section of tail flue.The application of SNCR had almost no impact on unburned carbon, exit gas temperature and CO emission, but the amount of exit flue gas would be increased. So, there was a boiler efficiency loss of about 0.5% under the experimental conditions.