Characterization of Scale Substances Depositing on Hollow Copper Conducting Wires of Internal Cooling Water Generator

QIU Yan-Li,YANG Zhen-Guo
DOI: https://doi.org/10.3969/j.issn.1673-6214.2006.03.010
2007-01-01
Abstract:The scale substances deposited on hollow copper conducting wires of generator were characterized and analyzed to solve the problem of abnormal temperature rising of stator slots of a 300 MW generating unit. The experimental results showed that the scale substances were mainly PTFE binding resins, fiberglass bundles, sealant as well as copper oxide from corrosion; and the abnormal rising temperature of stator slots was due to scale substance blocking hollow copper conducting wires. Moreover, countermeasures for solving the problem were tentatively put forward, and the practical data and scientific basis for the long-term safety and stability operating of the generator were provided.
What problem does this paper attempt to address?