Analysis of Short-Circuit Current Exceeding Standard of Guangdong Power Grid and Research on Limitation Measures

LI li,LI Aimin,WU Kecheng,CAI Zexiang
DOI: https://doi.org/10.3969/j.issn.1674-0629.2009.z1.004
2009-01-01
Abstract:The main influencing factors, distribution characters and changing rules of short-circuit current exceeding standard of Guangdong and local power grids are analyzed, and it is pointed out that the short-circuit current at 500 kV side mainly depends on 500 kV power network configuration while the one at 220 kV side depends on the capacity of transformers and the 220 kV power network configuration.The limitation measures are proposed for 500 kV side such as to break the line, to adopt transformer with high impedance installation of neutral reactors, and for 220 kV side to handle with different ways according to the electromagnetic loop.The short circuit current limiter(SCCL) based on the thyristor protected serier compensation(TPSC) can partly resolve the exceeding standard problem of 500 kV side without influence of the transient stability and bus voltage, and the development of its practical device is an emphasis on future research.