Analysis on Low Voltage Releasing Accident of Load in Dongguan District

WANG Lin,XU Baiyu,WANG Yi,LI Xinran
DOI: https://doi.org/10.3969/j.issn.1007-290x.2013.02.007
2013-01-01
Abstract:Aiming at several large load loss accidents caused by phase-to-phase fault of lines of major network in pearl river delta of Guangdong power grid,this paper takes one low voltage releasing and load loss accident caused by L1 and L2 inter-phase short circuit ground fault of Dongguan 220 kV Dongli line on May 5th in 2012 as examples,analyzes reasons and impact in two aspects including voltage changes and load loss in Dongguan substations and proposes feasibilities suggestions for configuration of low voltage releasing apparatus.It proceeds simulation analysis on L1 and L2 inter-phase short circuit ground fault of Dongguan 220 kV Dongli line and inter-phase or three phase fault of alternative current system of 220 kV or above voltage in Guangdong power grid and the result shows that if there happens inter-phase or three phase fault in alternative current system,the reason may be trip of low voltage releasing apparatus caused by instant voltage sag of the system which may result in large load loss and abnormal frequency.