Foreign Body Caused Flashover on Composite Insulator in Wet and Contaminated Condition

JIA Zhi-dong,ZHANG Wei,FANG Su,GUAN Zhi-cheng,ZHU Ke-neng
DOI: https://doi.org/10.13336/j.1003-6520.hve.2010.08.010
2010-01-01
Abstract:We focused on the flashover mechanism on wet contaminated composite insulator when bird streamer dropping by the insulator using iron wires,and investigated the low temperature nature of silicon rubber.We think that the contamination layer on the insulator may be saturated when unexplained flashover typically occurs.The experiments on 110kV composite insulators were conducted in the laboratory to simulate the flashover process using iron wires.The results show that foreign bodies with length of 50~70 cm can cause the flashover on 110 kV composite insulators,and videos show that it is combination of surface discharge and air breakdown,while flashover won't occur on clean insulator in the same condition.Then simulation model is set up to investigate the mechanism of the flashover.It is believed that the electric field of the foreign body induces the flashover,and then pollution flashover occurs.Finally,these studies are used to explain unexplained flashover.
What problem does this paper attempt to address?