High-risk Region of Bird Streamer Flashover in High-Voltage Transmission Lines

Yuanxiang Zhou,Hanghai Hu,Xu,Jifeng Cui,Yichao Yuan,Zhenyu Li,Yuan Chen,Deming Yu,Qiong Nie,Xidong Liang,Zhicheng Guan
DOI: https://doi.org/10.1016/j.elstat.2009.01.048
IF: 1.942
2009-01-01
Journal of Electrostatics
Abstract:Bird-caused outages are more common and widespread than generally believed, and greatly threaten the safety of transmission lines. However, few reports are concerned with laboratory research of bird-caused faulting, especially in the case of long air gap insulators. This paper carried out experimental and simulation work on bird streamer flashover of 220kV insulators. It was found that the radial distance from the insulator axis shows great influence on the bird streamer flashover. Significant is that we also found a high-risk region of bird streamer flashover which can be restricted in an elliptical region located at the center of 220kV insulator string, the major and minor axes being 500mm and 250mm. The processes of flashover due to bird streamer are discussed in detail. Simulation work further demonstrates the existence of the elliptical region of high flashover risk, which is of significance for transmission line protection.
What problem does this paper attempt to address?