A Novel Scheme of Generator Differential Protection

Zhu Jiajie,Tai Nengling
2008-01-01
Abstract:In terms of the problems occurred during the generator ratio restraint differential protection operating,owing to CT saturation caused by external short circuit transient fault,maloperation may be occurred in. Moreover,a certain amount of out-flow current may exist on the primary side of generator or transformer at short circuit fault on windings. It can decrease the sensitivity of the protection,and sometimes even bring the protection in non-operation. This paper presents a novel scheme of the generator differential protection. The phaselet component is used for judging whether an external fault or an internal fault is happened. After that different restraining currents are chosen. The simulation results prove that the new scheme of generator differential protection can ensure better sensitivity than traditional one during internal fault,and better security during external fault.