A Differential Protection Scheme for Distribution Networks with Multiple T-connected Inverter-Interfaced Distributed Generators

Yunbo Li,Lanjun Yang,Lei Hu,Liang Zhang
DOI: https://doi.org/10.1109/icpre59655.2023.10353770
2023-01-01
Abstract:Inverter-interfaced distributed generators (IIDGs) connected to distribution networks may cause the failure of conventional three-stage current protection or current differential protection. In this paper a novel differential scheme for distribution networks with multiple T-connected IIDGs is proposed. After building and analyzing the positive-sequence equivalent circuit of distribution networks with multiple T-connected IIDGs and equating multiple IIDGs to single IIDG, the protection criterion of this scheme is constructed only according to electrical quantities at both ends of the protected line. A simulation in MATLAB of a distribution network with multiple T-connected IIDGs is built to validate this proposed protection scheme. The feasibility and reliability of the proposed protection scheme are proved by the results of case studies.
What problem does this paper attempt to address?