Analysis and Simulation of Transformer DC Bias and Measures of Suppression in Hami Region

Zhang Don
Abstract:As the ± 800 kV HVDC converter station in Hami region is put into operation, the monopolar ground or asymmetric operation mode in DC system once appears, it will have an adverse effect on the AC power grid in the region. In this paper, combination with the features of the regional power grid and the earth soil resistivity in Hami, the transformer DC bias condition is measured in 300 km range round the DC grounding electrode when DC monopolar debugging. Then, the electromagnetic transient model of AC/ DC system and the equivalent earth resistance model are established according to the power structure in Hami. The models are checked by the measured data based on the inversion method. The DC current distribution characteristics of the transformer neutral in the substation around Hami are obtained when earth return line is in operation. For some transformer in which the DC current flowing through their neutrals is relative higher, the method of series capacitors in neutral is used to suppress the DC current according to the features of power grid in Hami, and the suppression applicability is analyzed.
Engineering,Environmental Science,Physics