Measures to Restrain the Neutral Current of the AC Transformer in HVDC Ground Return System
Rong ZENG,Jie ZHAO,Chun SHANG,Xiao-lin LI,Qi WANG,Ben NIU,Jin-liang HE,Bo ZHANG
DOI: https://doi.org/10.13336/j.1003-6520.hve.2009.04.037
2009-01-01
Abstract:The influences, such as sharp rising of the audible noise, harmonic and oscillation, will be found in the power system and transformer, where the HVDC transmission system operated in ground return mode. Based on the analyzing of the characteristics of the DC current distributed under ground and in the AC network, some useful measures, such as the optimization of the location of the substation and the DC grounding system, being operated with additional metal return wire, several HVDC substations sharing one grounding system, suitable structure selection of transformer, were put forward. Some measures to decrease the neutral current, such as the injection of reverse DC current, blocking capacitor and blocking resistor, were compared. Moreover, the resistor blocking solution was recommended, and some useful conclusions were drawn.