Assessing High-Voltage Shore Connection Safety: An In-Depth Study of Grounding Practices in Shore Power Systems

Shih-Hsien Hsu,Fu-Ming Tzu,Wei-Huang Chang,Yi-Dong Chen
DOI: https://doi.org/10.3390/en17061373
IF: 3.2
2024-03-14
Energies
Abstract:There is growing concern regarding air pollutants (NOx, SOx, and PM) and carbon emissions from ocean-going vessels in harbor areas and the role of high-voltage shore connection (HVSC) systems in mitigating these emissions during vessel berthing. The HVSC operates as a TN grounding system in humid environments, and it needs a proper grounding design to ensure safety when faults occur. This article intends to examine the overvoltage resulting from fault currents and its implications for the safety of operators when a single line-to-ground fault takes place within the design of HVSC grounding systems. The assessment is carried out by employing actual scenarios and parameters from a container berth at Kaohsiung Harbor in Taiwan. Considering site conditions, such as the wet ground surface, human body resistance, and electric shock duration, the tolerable safe voltage level is derived using IEEE Std. 80 and IEC 60479-1. Based on the shore power system grounding architecture specified in IEEE/IEC 80005-1, an equivalent circuit model is constructed to calculate the fault currents using symmetrical component analysis. The actual touch voltages generated in various locations are analyzed under scenarios of connecting or disconnecting the equipotential bonding between the ship and the shore using neutral grounding resistor (NGR) designs. This article delves into the scenarios of electric shock that may occur during the operation of an actual container ship's shore power system. It evaluates whether various contact voltage values exceed current international standards and verifies the grounding design and safety voltage specifications of IEEE/IEC 80005-1. According to the results of this study, the use of NGR and protective earthed neutral (PEN) conductors in HVSC is crucial. This can limit fault currents, reduce touch voltage, and ensure the safety of personnel and equipment. Therefore, ensuring and monitoring equipment conductors and adopting NGRs of appropriate sizes are crucial elements in maintaining electrical safety in HVSC systems.
energy & fuels
What problem does this paper attempt to address?
### Problems Addressed by the Paper The paper primarily explores the safety grounding design issues of High Voltage Shore Connection (HVSC) systems during ship berthing. Specifically, the paper focuses on the following aspects: 1. **Impact of Fault Current**: - When a single-phase ground fault occurs, the overvoltage in the HVSC system can pose safety hazards to operators. The paper evaluates this overvoltage and its impact on operator safety through real scenarios and parameters. 2. **Safety Voltage Standards**: - Based on IEEE Std. 80 and IEC 60479-1 standards, considering factors such as humid environments, human body resistance, and duration of electric shock, the paper derives acceptable safety voltage levels. 3. **Design of Equipotential Bonding**: - Constructing an equivalent circuit model to calculate fault current based on the grounding architecture of shore power systems specified in IEEE/IEC 80005-1 standards, the paper analyzes the contact voltage generated when the equipotential bonding between the ship and shore is connected or disconnected under different conditions. 4. **Role of Neutral Grounding Resistor (NGR)**: - The study finds that using a Neutral Grounding Resistor (NGR) and Protective Earth Neutral (PEN) conductor can limit fault current, reduce contact voltage, and ensure the safety of personnel and equipment. Through the above research, the paper aims to validate the grounding design and safety voltage specifications in IEEE/IEC 80005-1 standards and propose key measures to ensure electrical safety.