Measurement and Safety Criteria of Step Voltage of High Voltage Direct Current Grounding Electrode

Hailiang Lu,Jiahao Chen,Bo Tan,Jianwu Wang,Wei Chen,Shangmao Hu,Shijun Xie,Hansheng Cai,Wei Li,Sen Wang,Xishan Wen
DOI: https://doi.org/10.1109/tpwrd.2021.3061465
IF: 4.825
2022-02-01
IEEE Transactions on Power Delivery
Abstract:Grounding electrode is an indispensable part in HVDC transmission projects. During its design and safety evaluation, step voltage is a crucial aspect. By reviewing and sorting out the present standards involving step voltage measurement and its safety limit, this paper illustrates the contradiction between the measurement methods and the safety evaluation criteria. Reasons for the contradiction are explained by analyzing the principal of step voltage measurement and safety evaluation. The Open-circuit step voltage measurement method and the measurement method with a human body equivalent resistance paralleled are compared to find out their advantages and disadvantages. Suitable circumstances and corresponding safety criteria of these two methods are put forward. Method proposed in this paper can be applied to step voltage measurement and safety evaluation of HVDC grounding electrode, providing reference when revising the related standards.
engineering, electrical & electronic
What problem does this paper attempt to address?