Discussion of Earthing Design Safety Criteria for AC Power Plant and Substation Grounding System

YANG Huai-dong
DOI: https://doi.org/10.3969/j.issn.1671-9913.2013.03.013
2013-01-01
Abstract:Safety for person and equipment is the main purpose of power plant and substation grounding system design.The safety criteria defined in the domestic grounding design standard "GB 50065-2011: Code for design of ac electrical installations earthing" and the international grounding design standard "IEEE Std 80-2000: IEEE Guide for Safety in AC Substation Grounding" are different.According to the analysis of them,application scope for personal safety criterion is presented.At the same time,limitation of equipment safety criterion in these two standards is pointed out.And based on the equipments’ insulation level,arrangement and actual running situation in the power plant and substation,it is recommended for the first time to use the maximum relative potential rise inside the power plant or substation grounding system as the equipment safety criterion.For large area or high soil resistivity power plant and substation,it can greatly improve the economical efficiency.