Lightning Overvoltage Analysis of a 380-kV overhead line with a GIL

M. Kizilcay,C. Neumann
Abstract:A new underground 380-kV gas-insulated line (GIL) of length 400 m has been built near a 380-kV substation to replace an existing overhead line section in an industrial area to gain space for additional buildings. The last 600 m line section between GIL and substation remains as 380-kV overhead line. The power transmission capacity of the GIL amounts to 2000 MVA per circuit. The lightning overvoltage stress and lightning protection of that 380-kV GIL section has been studied in this paper. The lightning overvoltages caused both by back-flashover over the line insulator and by direct lightning strokes are taken into consideration.