Analysis and Research on the Reasons for the Increase of Com ponents in 500kV Transformer Oil

Rui Li,LiangYuan Chen,DaJian Li,Lei Zhang
DOI: https://doi.org/10.1088/1742-6596/2290/1/012026
2022-06-22
Journal of Physics: Conference Series
Abstract:This paper analyzes the cause of the defect of component growth in a 500kV transformer oil. First, the historical operation of the main transformer is analyzed, and then the oil chromatography data is studied. The A-phase online chromatography shows that the acetylene content is in good agreement with the offline chromatography detection, showing an increasing trend. The disintegration inspection of the main phase A phase found that there were two obvious discharge breakdown points in the inner paper tube of the low-voltage coil. According to the analysis results, the A-phase transformer should be managed and controlled, especially the oil chromatography tracking period (once every two weeks) should be shortened, and the load should be controlled if necessary.
What problem does this paper attempt to address?