Experimental Investigation on an Absorption Heat Transformer for Production of Hot Water or Steam Generation

Feng Liu,Yang Jing,Taixiu Liu,Jun Sui,Yujie Xu
DOI: https://doi.org/10.1007/s11630-020-1406-z
IF: 2.013
2021-01-03
Journal of Thermal Science
Abstract:The absorption heat transformer is widely used to utilize low-temperature waste heat in the field of distributed energy, industrial processing, and long-distance indoor heating, because it can upgrade energy level and deliver heat to heated medium. In this work, an experimental system of a vertical single-stage LiBr/H2O absorption heat transformer was established to study its performance in the case of producing high-temperature water or low-pressure steam generation under different heating water flow rates. The useful output heat, coefficient of performance, exergy coefficient of performance, and gross temperature lift of the single-stage heat transformer have all been tested. The results show that the absorber cannot directly generate low-pressure steam under the condition of counter-flow heat exchange but can obtain more useful output heat. The largest useful output heat is 20.3 kW, which is higher than that in the case of parallel-flow heat exchange. The generation of low-pressure steam has certain requirements on the mode of heat transfer. The largest internal gross temperature lift of 28.1°C corresponds to the smallest coefficient of performance of 0.22 when the heating water flow rate is 2.1 m3/h. The performance of the single-stage absorption heat transformer can be improved to some extent by increasing the heating water flow rate.
engineering, mechanical,thermodynamics