Design and Experimental Study of a Second Type Absorption Heat Exchanger

Jingtong Hu,Xiaoyun Xie,Yi Jiang
DOI: https://doi.org/10.1016/j.ijrefrig.2020.05.030
IF: 4.14
2020-01-01
International Journal of Refrigeration
Abstract:Absorption heat exchanger(AHE), as a kind of heat transformation device, is widely used in long-distance heat transportation system, waste heat recovery and other heat exchange processes s with large flow ratio on both sides. A second type of absorption heat exchanger was first designed, manufactured, and tested to get the performance in this research. The falling-film prototype absorption heat exchanger is consisting of a multi-section absorption heat transformer and a plate heat exchanger, using LiBr-H20 as working fluid. Under different working conditions, the tested results showed that the outlet temperature of the heat sink water was 916 K higher than the inlet temperature of the water on the heat source side. The coefficient of performance (COP) of the absorption heat transformer (AHT) was between 0.33 and 0.42. The temperature efficiency of the absorption heat exchanger was 1.24-1.35. Finally, the simulation model used to design the prototype machine was verified by the test results. (C) 2020 Elsevier Ltd and IIR. All rights reserved.
What problem does this paper attempt to address?