Performance Analysis on the Large Temperature Lift/Drop Multi-stage Vertical Absorption Temperature Transformer

Wang Sheng,Xie Xiaoyun,Jiang Yi
DOI: https://doi.org/10.3969/j.issn.0253-4339.2013.06.005
2013-01-01
Abstract:The reasons for the problems of the existing absorption heat exchangers,such as excessively large size,high manufacture costs,and high return temperature of the primary network hot water,were attributed to the"triangular heat transfer processes"inside the absorption heat pumps.The structures of new Multi-stage Vertical Large Temperature Lift/Drop Generation-condensation And Evaporationabsorption Elementary Units were introduced,as well as their principles on how to eliminate the"triangular heat transfer processes"with a relatively compact structure.A new type of the absorption heat exchanger,called the Multi-stage Vertical Large Temperature Lift/Drop Absorption Temperature Transformer(ATT),was constituted by such elementary units.Simulation models for the ATT were built to compare its performance to the traditional single-stage absorption heat exchanger.Results showed that the ATT can reduce the minimum return temperature of the primary network hot water,from 26℃ to under 20℃.When return temperature of the primary network hot water is 26℃,the ATT can reduce the total KA(heat transfer areas multiplied by heat transfer coefficients) by 25%~32%,while the powers of solution pumps inside the ATT were only increased by 19%~48%,which were not remarkable.The ATT has obvious performance advantages over the traditional single-stage absorption heat exchanger.
What problem does this paper attempt to address?