Analysis and Prevention Treatment for Rain Flashover Accident of ±500 Kv Composite Bushing

Yang Shen
2015-01-01
Abstract:Rain flashover is a large proportion of external insulation accidents in HVDC transmission. A rain flashover accident of ±500kV composite bushing is analyzed. After analyzing the accident causes, the existing shortcomings in external insulation design of DC bushing are found out.The corresponding method for improvement and treatment are proposed by aspect of optimizing external insulation design and using booster shed. Design and installation technology for booster shed is researched in the light of lacking of examples of installing booster sheds on composite silicone insulation. Structure design, material performance, simulation experiment, installation process of new spiral booster shed are introduced, which provide the experiences to external insulation design and antirain flashover technology of DC devices for the future HVDC transmission system.