Abstract:Taking the valve cooling system of Nanqiao converter station as an example,its problems and the transformation process are presented.Then,the valve cooling system protection theory and its settings are introduced.The HVDC outage accidents caused by valve-cooling system in recent years are listed and analyzed.The defect distribution of inner and outer valve cooling system in the six domestic HVDC transmission projects is illustrated.The hidden danger of single or dual poles blocking includes single sensors, power lost,water leakage,wrong settings,etc.Their corresponding countermeasures are also presented.After taking the necessary corrective and remedial measures,the HVDC forced outage rate is greatly reduced.