Experimental Investigation of Heat Transfer Characteristics of Louver Fin-and-tube Heat Exchanger with 5 Mm Diameter Tubes under Wet Conditions

Gao Jing-dan,Guoliang Ding
2012-01-01
Abstract:The heat transfer characteristics of fm-and-tube heat exchangers with 5 mm diameter tubes under wet conditions were investigated by experiments on 11 louver fm-and-tube heat exchangers.The effects of fin pitch and inlet relative humidity on air-side performance were analyzed.The results indicated that the effect of inlet relative humidity on the heat transfer rate is small,and heat transfer rate decreases with the increase of fin pitch, which is more obvious than that of fm-and-tube heat exchanger with 7 mm or larger diameter tubes.The water bridge was observed at the bottom of fin in experiments;however,it did not occur on the fin with 7 mm or large diameter tubes.A correlation for j factor was developed to predict the heat transfer performance of fm-and-tube heat exchanger with 5 mm diameter tubes.The deviations of the proposed j correlation are within±20%.
What problem does this paper attempt to address?