Research on Frequency Response Compensation Measures of Operated Resistive?capacitive DC Voltage Divider

XIAO Yong,ZHAI Shaolei,LUO Yi,WANG En,QIAN Bin,WEI Ling
DOI: https://doi.org/10.14044/j.1674-1757.pcrpc.2023.02.006
2023-01-01
Abstract:The frequency response characteristic of resistive-capacitive DC divide is very important to the control and protection system of the HVDC transmission system. During the operation period of the resistive-capacitive DC voltage divider,such faults as insulation flashover and dielectric breakdown may occur inside the divider,which leads to variation of its equivalent capacitance and thus leads to variation of its frequency response. Since it is difficult to measure the resistive-capacitive parameters of the operated DC divider directly and to quantify the compensation resistive-capacitive parameters,a kind of indirect measurement method of operated resistive-capacitive parameters of the operated resistive-capacitive DC voltage divider and frequency response compensation measures are proposed on the research status to measure indirectly the resistive-capacitive parameters of operated resistive-capacitive DC voltage divider through test result of frequency response of the secondary side under standard capacitive load and,in accordance with parameter balance formula of the resistive-capacitive voltage divider,to adjust the capacitive parameters of the low voltage arm so to achieve compensation of frequency response characteristic resistive-capacitive voltage divider. The simulation result shows that the proposed method can achieve frequency response compensation of the operated resistive-capacitive voltage divider.
What problem does this paper attempt to address?