Study on Ferroresonance Caused by Breaker Parallel Capacitance

Shen Yi,Chen Shui-ming,Chen Gang,Gao Wen-hui,Dong Hua-lu
DOI: https://doi.org/10.3969/j.issn.1003-9171.2006.03.003
2006-01-01
Abstract:According to a ferroresonance accident occurred at one 220 kV station in Beijing,Authors use electromagnetic transient simulation software to simulate the probability of ferroresonance occurrence when inductive voltage transformer connected to the station's 220 kV bus line and breaker parallel capacitance form a resonance circuit.According to some ferroresonance restraining measures,the inductive voltage transformers are replaced with capacitive voltage transformers.Finishing 500 switch operations,some results are obtained.When bus was connected with inductive voltage transformer,there is high possibility to occur ferroresonancc when doing switch operations.While using capacitive voltage transformer,there is no such possibility.Therefore,to replece inductive voltage transformer with capacitive voltage transformer is a good measure to restrain ferroresonance.
What problem does this paper attempt to address?