Performance Of Point Type Smoke Detectors In Iso Fire Tests Under Different Altitude Areas

Tu Ran,Yu Chunyu,Chen Hong,Fang Jun,Wang Jinjun,Zhang Yongming
2010-01-01
Abstract:The response of ordinary point type fire smoke detectors under Hefei and Lhasa was studied using 4 kinds of ISO test fires. Because of difference in altitude, the atmospheric pressure in Lhasa is about 2/3 of that in Hefei, so is the air density, due to change of O(2) density, fuel burning behavior was also different in two places. Comparison experiments were conducted in ISO fire test rooms of Hefei and Lhasa respectively based on ISO detector test method. Point type detectors such as light scattering photoelectric detectors and ionization detectors were used for the 4 test fires including 2 kinds of smouldering fires and 2 kinds of flaming fires, smoke soot size characteristics were also studied by SEM system. According to comparison experiments, The results show that the detector signal variation of smouldering test fires in two places is very different from flaming test fires, for the flaming test fires, the photoelectric detector signal in Lhasa appeared much lower than that in Hefei, combining the effects of fire dynamics and soot formation by air pressure, a qualitative analysis was given in this work.