Abstract:To study the working performance of contact smoke detectors in large space fire,numerical wind tunnel experiments and ASPIRE2 program were adopted respectively to model the process of smoke entering the sensing chamber of two kinds of detector products:spot-type smoke detector and air sampling smoke detector.On the basis of FDS fire simulation of a certain gymnasium,the performance evaluation of the two detector products were proposed based on the alarm threshold of obscuration.The analysis results show that the spot-type smoke detectors fail to detect small fires;while the effect of air sampling detection is significantly influenced by the arrangement of pipe networks.The assembled sampling,which combines ceiling and vertical pipes,can overcome the adverse effect of thermally stratified environments,and have high coping ability in various fire situations,especially for small fires.