Abstract:The purpose of this paper is to present the experimental supports for the type selection of fire detectors when fire alarm systems are designed. Experiments were performed to evaluate and compare the sensitivity of photoelectric and ionization smoke detectors in the Fire Emulator/Detector Evaluator, using the typical smoke generated by the fuels of four standard fires addressed in the code. The results indicated that the outputs of photoelectric detector increased more sharply than ionization detectors for the smoke generated by pyrolyzing wood. However, for the smoke generated by the smoldering cottons, flaming polyurethane foam and flaming heptane, the ionization detectors respond more sensitively than the photoelectric detectors. Finally it is suggested that the fire alarm system should be designed by selecting suitable fire detectors based on the possible fuels in the building.