INFLUENCE ON PERFORMANCE OF SMOKE FIRE DETECTORS BY VELOCITY

谢启源,袁宏永,宋立巍
DOI: https://doi.org/10.3969/j.issn.1009-6094.2004.01.017
2004-01-01
Applied Mechanics and Materials
Abstract:The objective of this paper is to evaluate the performance of photoelectric and ionization smoke detectors in different smoke velocities through the Fire Emulator/Detector Evaluator(FE/DE) developed by the State Key Laboratory of Fire-prevention Science (SKLFS) recently. The present research provides some powerful experimental supports for the selection of smoke fire detectors in particular. To bring the research into a full success, a series of experiments has been done with the smoldering cottons as the smoke source, and with the velocities 0.5 m/s, 1.0 m/s, 1.5 m/s, 2.0 m/s, 2.5 m/s, 3.0 m/s, 3.5 m/s, 4.0 m/s, 4.5 m/s, 5.0 m/s and 5.5 m/s, respectively. The same amount of smoldering cottons has also been used in each experiment to ensure the changing parameter between these experiments to keep the air velocity around the smoke detectors. In this way, it is possible to clearly observe the different responses of photoelectric and ionization smoke detectors in different smoke velocities. The research results indicate that the sensitivity of the photoelectric smoke detector decreases sharply while the velocity around it keeps increasing. However, under the same condition, the sensitivity of the ionization smoke detector does not drop abruptly as the photoelectric detector remains at the same level. Therefore, the preliminary analysis proves that such a phenomenon is accounted with differences in smoke-sensing principles and smoke tunnels' structures between these two kinds of smoke fire detectors.