Heating performance optimization of a two-stage compression air source heat pump based on simulation

Shuang JIANG,Shugang WANG,Feng WANG
DOI: https://doi.org/10.3969/j.issn.2095-2783.2017.01.005
2017-01-01
Abstract:A simulation model for a two-stage compression heat pump system with variable capacity was developed and verified by experimental data in this study, which was used to study the optimum heating performance of the system in operation.The results indicate that there is a linear relationship between the optimum operating frequency of the low-stage compressor and the environment temperature when the condensation condition is fixed.The lower the environment temperature, the larger is the optimum low-stage compressor frequency.The optimum intermediate pressure is higher than the geometric average pressure, with a ratio between 1.20 and 1.56.The regressed optimum frequency formula is based on evaporating and condensing temperature or pressure with a simple form, which meets the need for system control.
What problem does this paper attempt to address?