RESEARCH ON TWO- STAGE COMPRESSION VARIABLE FREQUENCY AIR SOURCE HEAT PUMP IN COLD REGIONS

田长青,石文星,王森
DOI: https://doi.org/10.3321/j.issn:0254-0096.2004.03.026
2004-01-01
Abstract:A two-stage compression variable frequency air source heat pump (TV-ASHP) has been developed combining variable frequency technology with two-stage compression cycle. The empirical formula of optimal intermediate pressure was calculated, and two control model with the priority target as coefficient of performance (COP) or heating capacity was advanced. It is demonstrated by the experimental investigation and theoretical analysis that COP of this heat pump system is over 2, the compressor discharge temperature under 120°C, and the heating capacity can meet the heating load needed when the condensing temperature is 50°C and evaporating temperature -25°C. Also the experiment shows this system runs safely and steadily, which can be used in the cold regions where outdoor temperature over -18°C.
What problem does this paper attempt to address?