Experimental Research on Quasi Two-stage Compression Heat Pump with Flash Tank Vapor-injection Using R134a
Yupeng Chai,Guoyuan Ma,Shuxue Xu,Ruochen Ding,Lihua Yu
DOI: https://doi.org/10.3969/j.issn.0253-4339.2017.02.011
2017-01-01
Abstract:In order to improve the stability and coefficient of performance of the air source heat pump,a scroll compressor refrigeration/ heat pump system with flash tank was proposed using R134a,and the experiment platform was built.The compressor's discharge tempera ture,power input,cooling capacity,heating capacity,coefficient of performances of the refrigeration/heat pump system were studied.Resuits showed that,under the condition of condensing temperature 45 ℃ and evaporating temperature from-20 ℃ to 0 ℃,the discharge temperature of the vapor injection system was 6.2 ℃ lower than that of the single stage compression system,power input increased only 1.4% to 2.8%,the cooling capacity and cooling COPc are 19.8% and 17.6% higher than that of the single stage system,the heating capacity and heating COPh are 15.3% and 13.2% higher,respectively.