Evaluation on Operation State and Stability for Denitrification of Ultra Low Emission

LI Qing-yi,MENG Wei,WU Guo-chao,ZHANG Jun,ZHU Song-qiang,HU Da-qing,ZHENG Cheng-hang,GAO Xiang,WANG Ru-neng,LIU Hai-jiao
DOI: https://doi.org/10.3785/j.issn.1008-973x.2016.12.009
2016-01-01
Abstract:The evaluation system for the performance of denitrification device was established by taking the 1 000 MW coal-fired unit after ultra low emission transformation as an example .The operation ,reliability and stability of denitrification device was evaluated in detail . Results show that the qualified rates of selective catalytic reduction (SCR) inlet NO x concentration ,SCR outlet NO x concentration ,denitrification efficiency ,ammonia escape and pressure loss are 90 .45% ,92 .34% ,78 .98% ,92 .34% and 100 .00% , respectively ,while the corresponding evaluation standards are 300 mg/m3 、50 mg/m3 、85% 、3 × 10 - 6 and 600 Pa ,respectively .Substandard working conditions occurs at the operation state of variable and low load .The main reasons are that the response rate of spray ammonia signal is too slow ,that the oxygen content in the furnace is difficult to control and that the SCR inlet temperature is too also low .The average NO x concentration at SCR outlet after reformation decreases significantly ,even lower than 30 mg/m3 .The NO x concentration at the outlet of the chimney is stable and reliable with the qualified rate of 98 .74% , which is even higher than the designed value .