Effects of Boiler Control Mode on Ammonia Escape of the SCR System in a 660 MW Ultra-supercritical Unit

YANG Jianguo,HU Jinyi,ZHAO Hong,WAN Chaohui,KANG Kewei,CHEN Lishuai,ZHOU Ailin
DOI: https://doi.org/10.3969/j.issn.1674-7607.2015.06.008
2015-01-01
Abstract:The experimental tests were carried out to a 660 MW ultra-supercritical unit to study the effects of boiler control mode on the ammonia escape.Results indicate that the ammonia escape rate would increase with the rise of denitration efficiency.Especially when the denitration efficiency is higher than 65%(designed value),the increasing rate would be larger.The NOxconcentration at SCR's inlet has an optimum value(about 200mg/m3)to corresponding the lowest ammonia escape rate.The ammonia escape rate would increase obviously with higher SOFA rate(optimum value is 18%)or oxygen concentration(optimum value is 3%),which would decrease with the reduction of unit load.When the unit load drops to 500 MW or lower,the ammonia escape rate would decrease by about 60%.