Abstract:A unified model for harmonics and reactive current closed-loop or open-loop detection was established based on instantaneous reactive power theory. The fundamental active currents were obtained by transforming the load currents into rotation coordinate system and filtering the high frequency component through an equivalent lowpass filter. Harmonics and reactive currents were acquired by subtracting the fundamental active currents from load currents. An optimum project was presented for the equivalent lowpass filter, and the effects of the rank and cutoff frequency of the filter on the dynamic and static features of the detection system were analyzed. Considering the performance of both dynamic and static response, the cutoff frequency should be 10—40 Hz. The rank should not exceed 3 for reducing the realization complexity. The experimental result of a realtime harmonics and reactive current closed-loop detection system applied to active power filter shows that this system has perfect dynamic and static response.