A Current Control Method for LCL Active Power Filters Based on the Reduced Order Generalized Integrator

YANG Jiaqiang,YANG Lei,ZENG Zheng,SU Zipeng
DOI: https://doi.org/10.13334/j.0258-8013.pcsee.160756
2017-01-01
Abstract:In order to implement the stable control of active power filters (APF) with LCL filters without increasing the system complexity, a current dual-loop control method is proposed on the basis of source current detection and inverter-side current feedback. Without the additional current sensors, the active damping for the resonance peak of LCL filters is implemented by introducing inverter-side current feedback. Meanwhile, in order to accurately track source harmonic currents, the reduced order generalized integrator (ROGI)-based current controller is proposed on the basis of the second order generalized integrator (SOGI). High harmonic compensation precision and computing efficiency are both realized because ROGI is sensitive to both frequency and sequence. Finally, the proposed method is proved to be valid by experiments on a 50kVA APF with LCL filter.
What problem does this paper attempt to address?